Methodology and assumptions

Radiator BTU / Room Heat Calculator (UK)

This tool estimates the steady-state heat loss of a single rectangular room so you can plan radiator purchases. Fabric losses use Q = A × U × ΔT. Ventilation / infiltration uses Qv = 0.33 × V × N × ΔT, where the factor 0.33 approximates cpρ/3600 (CIBSE Guide A / common UK practice). A configurable planning allowance (default 10%) is then applied. The total is calculated without intermediate rounding, then rounded up to the nearest 50 W; a value of exactly 500 W remains 500 W. BTU/h is calculated only from the already-rounded watt figure using 1 W = 3.412142 BTU/h (NIST), then shown as a whole number.

Conservative and indicative defaults

Radiator comparison

Radiator catalogue outputs should be compared at ΔT50 under BS EN 442. Correcting a catalogue figure to another water temperature first computes an intermediate continuous watt value via Q = Q50×(ΔT/50)n, then applies the same R-01 rule (round up to the nearest 50 W) for the displayed result; BTU/h is taken only from that rounded watt figure. The intermediate value is not shown as the final answer. Educational only — not an MCS-certified system design.

Limits

This estimate does not replace a qualified heating engineer, a Gas Safe registered installer, or a full BS EN 12831 / MCS heat-load calculation.

Primary references